RQQ 1x240 1kV

Description

Description

Standards

  • Test
    EN 50268; IEC 60754
  • National
    SS 424 14 18

RQQ (S1Z1Z1-F) is a halogenfree, HFFR-insulted and -sheathed cable with circular and multi stranded copper conductor. The cable is designed according to SS 424 14 18. The conductors have resistance according to IEC 60228 class 5. The sheath is marked "NEXANS GS AREA mm2 1kV Dca2d2a2 year+month". RQQ meets the requirements for flame class Dcas2d2a2 according to CPR.

Lifemark(TM) recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recykling.

Quality system

Designed, manufactured and tested in accordance with ISO 9001.

Environmental management system

The activities at our plant in Grimsås are certified to ISO 14001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Round, shiny, flexible
Insulation
HFFR
Outer sheath
HFFR (Halogen Free Flame Retardant)
Halogen free
Yes
Colour
Black
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
240 mm²
Conductor diameter
21.3 mm
Average insulation thickness
2.2 mm
Average sheath thickness
1.8 mm
Nominal outer diameter
29.5 mm
Approximate weight
250.0 kg/100m
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Conductor electrical resistance
0.08 Ohm/km
Operating voltage
1 kV
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Minimum installation temperature
0 °C
Length
500 m
Maximum operating temperature
70 °C
Packaging
K14
Short-circuit max. conductor temperature
150 °C
Bending factor when installed
8 (xD)
U.V resistance
Very good

Resources

Resources

Selling & delivery Information

RQQ will be delivered in lengths of 500 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Declaration of Performance

  • Declaration of Performance n� : 1000173-SEGR
  • Certification Date : 1/27/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close