Earthconductor CCS
Earthconductor CCS
Conductor for use in the network as earthconductor. The conductor have in the center a wire of copper-plated steel (CCS).
Read moreJordlina CCS 25
Nexans ref. 26000098-201-05
- Packaging: Drum (500m)
- Approximate weight: 232 kg/km
- Conductor cross-section: 25 mm²
- Nominal outer diameter: 7,3 mm
- Max. DC resistance of the conductor at 20°C: 0,75 Ohm/km
Jordlina CCS 35
Nexans ref. 26000198-201-05
- Packaging: Drum (500m)
- Approximate weight: 327 kg/km
- Conductor cross-section: 35 mm²
- Nominal outer diameter: 8,2 mm
- Max. DC resistance of the conductor at 20°C: 0,524 Ohm/km
Jordlina CCS 50
Nexans ref. 26000298-201-05
- Packaging: Drum (500m)
- Approximate weight: 456 kg/km
- Conductor cross-section: 50 mm²
- Nominal outer diameter: 9,5 mm
- Max. DC resistance of the conductor at 20°C: 0,387 Ohm/km
Description
Description
Standards
-
ProductIEC 60228
Description
The conductor have resistance according to SS-EN 60228. In the center there is a wire of copper-plated steel (CCS) and the conductor is coated with black conductive plastic. In order to facilitate siting, the conductor is annealed. The CCS conductor is coated with semiconductive PE which shall be removed before connecting.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 2
Conductor material
Bare copper and clad steel
Conductor shape
Round, stranded
Number of conductors
1
Usage characteristics
Usage characteristics
Short-circuit max. conductor temperature
370 °C