AXQJ TT 24 kV 1x95/25
AXQJ TT 24 kV 1x95/25
The cable has a circular aluminium conductor, XLPE-insulation, copperscreen, AL/PE-tape and PE-sheath.
Read more- Nexans ref. : 21192198-201-05
Description
Description
Standards
-
ProductHD 620.10K
-
NationalSS 424 14 16
Design
- Conductor Circular, stranded aluminium conductor with resistance and number of wires according to SS 424 14 08. The conductor is longitudinally water blocked according to SS 424 14 17.
- Inner conducting layer Semiconducting crosslinked polyeten.
- Insulation Crosslinked dry cured polyeten (PEX).
- Outer conducting layer Crosslinked strippable conducting elastomer.
- Screen One layer of circular annealed copper wires, locked with swelltape.
- Moisturebarrier sheath Alongrunning plasticcoated aluminiumtape applied with glued overlap. The tape adheres the outher sheath.
- Sheath Black HFFR polyolefin. The sheath is marked, ie: "NEXANS NS AXQJ TT 12 kV 1 x 240/35 year month" + metremarking.
Lifemark(TM) recycling marking
The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.
Standards
The cable is in appliable parts constructed according to HD 620.5-K. The cable can be loaded according to SS 424 14 16.
Quality system
Designed, manufactured and tested in accordance with ISO 9001.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor shape
Round, stranded
Insulation
XLPE (chemical)
Outer sheath
HFFR (Halogen Free Flame Retardant)
Colour
Black
Halogen free
Yes
Conductor flexibility
Class 2
Conductor material
Aluminum
Screen
Copper wires / 6mm²
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Approximate weight
97,0 kg/100m
Average insulation thickness
5,5 mm
Average sheath thickness
1,9 mm
Conductor cross-section
95 mm²
Conductor diameter
11,3 mm
Diameter over insulation
25,1 mm
Nominal outer diameter
32,0 mm
Screen section
25 mm²
Electrical characteristics
Electrical characteristics
Approx. inductance, flat formation
0,64 mH/km
Approx. inductance, trefoil formation
0,38 mH/km
Earth leakage current at 20 kV
2.39 A/km
Max. DC resistance of the conductor at 20°C
0,32 Ohm/km
Nominal phase capacitance
0,2 µF / km
Operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Resistance of the screen
0,8 Ohm/km
Mechanical characteristics
Mechanical characteristics
Permissible pulling forces
0,03 kN/mm²
Usage characteristics
Usage characteristics
Minimum installation temperature
−10 °C
Recommended minimum installation temperature
0 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Water proof
Longitudinal & radial
Bending factor when installed
10 (xD)
Bending factor when laying
15 (xD)
Length
500 m
Packaging
-
U.V resistance
Yes
Resources
Resources
Selling & delivery Information
The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.
Declaration of Performance
- Declaration of Performance n� : 1000167-SEGR
- Certification Date : 19.02.19
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 0366
- Declared performance : Dca-s2,d2,a2
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania