AXLJ-F TTCL 12 kV

Products

AXLJ-F TTCL 12kV 1x95/25

Nexans ref. 21205198

  • Packaging: Drum (1000m)
  • Conductor cross-section: 95 mm²
  • Nominal outer diameter: 26,0 mm
  • Approximate weight: 79,0 kg/100m

 

AXLJ-F TTCL 12kV 1x150/25

Nexans ref. 21205298

  • Packaging: Drum (1000m)
  • Conductor cross-section: 150 mm²
  • Nominal outer diameter: 29,7 mm
  • Approximate weight: 102,0 kg/100m

 

AXLJ-F TTCL 12kV 1x240/35

Nexans ref. 21205398

  • Packaging: Drum (1000m)
  • Conductor cross-section: 240 mm²
  • Nominal outer diameter: 34,0 mm
  • Approximate weight: 142,0 kg/100m

 

AXLJ-F TTCL 12kV 1x630/35

Nexans ref. 21205698

  • Packaging: Drum (1000m)
  • Conductor cross-section: 630 mm²
  • Nominal outer diameter: 47,4 mm
  • Approximate weight: 288,0 kg/100m

 

Description

Description

Standards

  • Product
    HD 620 S2 2010 10M; IEC 60502-2

Description

AXLJ-F TTCL is a longitudinally and radial watertight, XLPE-insulated, copper wire screened, PE sheathed 1-core cable with circular aluminium conductor. The outer conductive layer on the insulation is crosslinked vulcanized elastomer. The cable is designed according HD 620 S2 2010 10M The conductor has resistance and number of wires according to IEC 60228 class 2.

Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc.

The sheath is marked type/manufacturer/year+month/metre marking. AXLJ-F TTCL is not flame retardant.

The sheath opens with cable tear thread.

 

The following applies if presstools are used:

The actual copperscreen are one cross section lower than the typemarking. This means that if the screen is 25 mm² the connector should be 16 mm².

Lifemark™ recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

Standards

The cable is constructed according to HD 620 S2 2010 10M. The cable can be loaded according to SS 424 14 16.

Quality system

Designed, manufactured and tested in accordance with ISO 9001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded
Insulation
XLPE (chemical)
Colour
Black
Conductor flexibility
Class 2
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Electrical characteristics

Electrical characteristics

Operating voltage
12 kV
Permissible short circuit current conductor 1s
- kA
Permissible short circuit current screen 1s
- kA
Rated Voltage Uo/U (Um)
7 / 12 kV

Usage characteristics

Usage characteristics

Minimum installation temperature
-20 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Water proof
Longitudinal & radial
Bending factor when installed
10 (xD)
Bending factor when laying
15 (xD)
Length
1000 m
Rip cord
Yes

Resources

Resources

Selling & delivery Information

AXLJ-F TTCL is delivered in lengths of 500 and 1000 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close